The most loved home mining system has become even better. More powerful than any alternative and fits every new immersion miner, including S21XP IMM. It’s the only immersion tank with build it pool heat exchanger, which makes it a first digital heat pump for home or pool heating!
DCX Bitpod 2 is the new and most powerful home mining immersion system available. In opposite to other proprieatry solutions made for one miner only, this immersion cooling tank can host any new immersion miner, including 3 MicroBt M56/66 Whatsminer or 2 new Bitmain S19XP IMM Antminers.
Capacity
Removes up to 80% of heat of the server, covering CPU and other components
Performance
From 330W to 760W of heat transfer performance using warm water
Sustainability
Requires ASHRAE W3/W4 (32-45C) water instead of power hungry chillers!
Compatibility
You can upgrade any server with Intel® processors with DCX HYDRO system coldplates
Overview
DCX Bitpod 2 is the new and most powerful home mining immersion system available. In opposite to other proprieatry solutions made for one miner only, this immersion cooling tank can host any new immersion miner, including 3 MicroBt M56/66 Whatsminer or 2 new Bitmain S19XP IMM Antminers. This unique single or dual loop immersion tank may be upgraded with dedicated pool or plate heat exchanger and connected directly to your home or pool, replacing power hungry heaters or heat pumps.
DCX Bitpod 2 is equipped with industrial pump, hydraulics and monitoring sensors with colour high-res LCD, remote temperature / status control and notifications. Typical applications: pool heating, water / boiler heating, floor heating. It’s the most universal and affordable home mining system, that can heat your home and earn money at the same time.
Features
-
3 x M56/66 Whatsminers or 2 x S21XP IMM Antminers!
-
Up to 20kW heat transfer!
-
Heat a swimming pool or home!
| Ninja Column 1 | Ninja Column 2 | Ninja Column 3 | |
|---|---|---|---|
| CPU Socket | LGA 4189 | ||
| Approach temperature | W3/W4 | ||
| Heat transfer capacity | [W] | 330 | |
| Heat transfer perfomance | [W/m²K] | 553 | |
| Thermal resistance | [K/W] | 0,039 | |
| Operating pressure | [kPa] | 600 | |
| Pressure drop | [Pa] | 354 | |
| Volume flow rate | [m3/h] | 0.022 | |
| Liquid inlet temperature | [°C] | [°F] | 32 | 90 | |
| Liquid outlet temperature | [°C] | [°F] | 45 | 113 | |
| Height | [mm] | 30 | |
| Active surface area | [m²] | 0.046 | |
| Filtering requirement | [μm] | 50 | |
| Ninja Column 1 | Ninja Column 2 | Ninja Column 3 | |
|---|---|---|---|
| Approach temperature | W3/W4 | ||
| Maximum heat transfer capacity | [W] | 2381 | |
| Heat transfer perfomance | [W/m²K] | 5176 | |
| Thermal resistance | [K/W] | 0.0042 | |
| Operating pressure | [kPa] | 600 | |
| Pressure drop | [Pa] | 7227 | |
| Volume flow rate | [m3/h] | 0.207 | |
| Liquid inlet temperature | [°C] | [°F] | 32 | 92 | |
| Liquid outlet temperature | [°C] | [°F] | 42 | 108 | |
Features
- Open system – compatible with every server
- Improves CPU & GPU performance
- Removes >80% of heat from the servers.
- Great for retrofitting, doesn’t void warranty
- Enables dense compute with 60kW per rack or more!
- Cools the systems with hot water (W3/W4 ASHRAE)
Get in Touch
We will advise, guide and support – the ideas are always free of charge!
Get your custom solution:
We need basic information to design custom liquid cooling system:
-
Quantity and general specification and dimensions of servers, ICT systems or other to be cooled components, along with power allocation per device or rack.
-
Brief overview of your project along with your main objective: better performance, water savings, energy efficiency, heat reuse, higher density?
-
Preferred liquid cooling technology: direct chip – coldplate system or immersion solution? Planned heat rejection or heat recovery strategy.
-
Country & city nearby planed location for climate data, heat transfer performance & shipping cost estimate.